Solar Panel Calculator

Get a first-pass solar sizing estimate — panel wattage and battery bank in watt-hours and amp-hours from daily use, sun hours, autonomy and system voltage. Runs entirely in your browser — your numbers never leave this device.

Panel size (estimate)
888.89 W
Battery bank 7500 Wh (312.5 Ah at 24 V)
Panels
888.89 W
Battery (Wh)
7500 Wh
Battery (Ah)
312.5 Ah
Daily use
3000 Wh
Sizing summary
ComponentSizeBasis
Solar array888.89 W3000 Wh ÷ (4.5 h × 0.75 derate)
Battery bank7500 Wh3000 Wh × 2 days ÷ 0.8 DoD
Battery bank312.5 Ah7500 Wh ÷ 24 V

This is a first-pass sizing estimate, not a system design: it does not size charge controllers, inverters, cabling or protection, and it is not a code-compliance check. Have a qualified installer verify a real installation.

How it works

Panel (W) = daily Wh ÷ (peak sun hours × derate) | Battery (Wh) = daily Wh × autonomy days ÷ depth of discharge | Battery (Ah) = battery Wh ÷ system volts | Derate defaults to 0.75

Off-grid sizing starts from energy, not power: how many watt-hours the loads consume in a day. The array must replace that energy during the available peak sun hours — the equivalent hours of full-strength sun your location and season deliver — after system losses, so panel watts = daily Wh ÷ (sun hours × derate). The default derate of 0.75 bundles the usual losses: inverter efficiency, cable drop, panel temperature and soiling. The battery bank is sized the other way, from storage: daily Wh multiplied by the autonomy days you want to survive without sun, grossed up by the depth of discharge you are willing to use — 0.5 for lead-acid longevity, around 0.8 for lithium — and converted to amp-hours at your system voltage.

Treat the output as a first-pass estimate for comparing options and budgets, not a system design. It does not size the charge controller or inverter (both are chosen on power and surge, not energy), cable gauges, fusing or earthing, and it uses a single sun-hours figure where a real design uses the worst month's figure for your location and panel tilt. Nothing here is a code-compliance check or an installation specification — have a qualified installer verify any system before it is built, and use the Electricity Cost Calculator to value the daily energy figure you start from.

Worked examples

A 3,000 Wh/day cabin on 24 V lithium

Input
Daily use = 3,000 Wh, Sun = 4.5 h, Derate = 0.75, Autonomy = 2 days, System = 24 V, DoD = 0.8
Working
Panels = 3,000 ÷ (4.5 × 0.75) = 3,000 ÷ 3.375 = 888.89 W. Battery = 3,000 × 2 ÷ 0.8 = 7,500 Wh, which at 24 V is 7,500 ÷ 24 = 312.5 Ah.
Result
Array ≈ 888.89 W · Battery 7,500 Wh (312.5 Ah at 24 V)

A 1,000 Wh/day load, one day of autonomy

Input
Daily use = 1,000 Wh, Sun = 5 h, Derate = 0.75, Autonomy = 1 day, System = 12 V, DoD = 0.5
Working
Panels = 1,000 ÷ 3.75 = 266.67 W. Battery = 1,000 × 1 ÷ 0.5 = 2,000 Wh = 166.67 Ah at 12 V — a lead-acid bank is only half usable, so the nameplate bank is twice the daily load.
Result
Array ≈ 266.67 W · Battery 2,000 Wh (166.67 Ah at 12 V)

A small 500 Wh/day system

Input
Daily use = 500 Wh, Sun = 6 h, Derate = 0.75 (default), Autonomy = 1 day, System = 12 V, DoD = 0.5
Working
Panels = 500 ÷ (6 × 0.75) = 500 ÷ 4.5 = 111.11 W. Battery = 500 ÷ 0.5 = 1,000 Wh = 83.33 Ah at 12 V.
Result
Array ≈ 111.11 W · Battery 1,000 Wh (83.33 Ah at 12 V)

Frequently asked questions

What are peak sun hours?

The day's total solar energy expressed as hours of full 1,000 W/m² sun — a location receiving 4.5 kWh/m² in a day has 4.5 peak sun hours, however the daylight was actually spread. Use the figure for your worst month, not the annual average, if the system must work year-round; solar atlases and PVGIS publish it by location and tilt.

Why is the derate 0.75, and should I change it?

It bundles the losses between the panel's nameplate and usable stored energy: temperature (panels produce less when hot), soiling, cable losses, charge-controller and inverter efficiency. 0.75 is the standard planning default; a DC-only system with short cables can justify 0.8–0.85, while hot climates and long runs argue for 0.7. It is a fraction, so enter 0.75, not 75.

What depth of discharge should I use?

The fraction of the bank you routinely use. Lead-acid lasts longest kept to about 0.5 — the 1,000 Wh example needs a 2,000 Wh bank for that reason — while lithium iron phosphate systems commonly plan on 0.8. Deeper discharge shrinks the bank you must buy and shortens its life; the trade-off is economic, and this field is where you price it.

Does this size my inverter and charge controller too?

No — those are power devices, sized from the largest simultaneous load (and its surge) and from the array's current, not from daily energy. This page sizes the two energy components, panels and battery bank, as a first-pass estimate. Controller, inverter, cabling and protection need their own calculations and a qualified installer's sign-off.

How many panels is 888.89 W?

Divide by the wattage of the panel you are buying and round up: 888.89 ÷ 400 W panels = 2.22, so 3 panels (1,200 W nameplate). Arrays are always rounded up to whole panels, and the spare headroom is useful — it covers the days that fall short of the average sun-hours figure you designed with.